Every minute, power grids worldwide dip in frequency — researchers at Germany's Forschungszentrum Jülich traced the pattern to uninterruptible power supplies checking their charge on the clock.

Row of electric transmission towers and power lines stretching across a field into the sunset
Photo: Unsplash / Matthew Henry

For years, grid operators from Europe to Australia, the U.S. to Malaysia have watched their networks’ frequency sag by a small amount every 60 seconds, with no clear explanation. Such dips, even when they fall short of causing blackouts, can damage power-plant equipment — particularly hydropower turbines — if left unaddressed. Dirk Witthaut, a researcher at Forschungszentrum Jülich in Germany, took on the puzzle after Germany’s largest transmission operator, Tennet Germany, brought it to him; it took years of modeling and investigation to find the cause.

The team first suspected hydropower plants, whose turbines can resonate at a frequency that amplifies vibrations — comparable to a wine glass shattering from sound. Modeling a hydropower control system on the Scandinavian grid, they found conditions that could produce a once-a-minute resonance, but not one that persisted indefinitely the way the real-world drops did. The clockwork regularity pointed instead to something literally running on a clock. Installing more than 80 smart power meters across the Jülich campus — itself equipped with battery backup systems — the researchers found the same once-a-minute spike on the transformer feeding the site’s battery storage. Many stationary batteries, including the uninterruptible power supplies (UPS) that back up data centers, check their state of charge every 60 seconds; because the devices are internet-connected, their internal clocks stay in near-perfect sync, turning individually invisible blips into a collective dent in the grid.

Ireland supplied the clearest evidence. Data centers accounted for 18% of the country’s electricity load by 2022, each backed by a fleet of UPS units. Between 2016 and 2021, the minute-by-minute frequency drop on Ireland’s grid quadrupled, from 3 milli-Hertz to 12 mHz, and some recent drops have exceeded 20 mHz. Ireland’s 50 Hz grid can absorb swings of 200 mHz in either direction, though the operator prefers to keep them under 100 mHz; if other loads push the frequency down at the same time, the added UPS effect could tip the grid toward blackout conditions. The team also found similar periodic fluctuations in IoT devices such as smart ovens and Raspberry Pi clusters, pointing to a problem that could outlast UPS fixes alone — a recent study found less than 3% of IoT devices run the latest firmware.

Why it matters

Witthaut’s team says the fix is simple — manufacturers randomizing when devices check their charge — but regulators may have to act, and each can only cover its own grid. Containing a disturbance that spans continents will ultimately take global coordination, and the problem could persist for years even with the mystery solved.